Fan Application Pressure Calculation

Non-Casing Fan Applications - Fan and Cabinet Dimension Requirements
Non-Casing Fan Applications - K Value and Constant Airflow Applications
Fan Parallel Connection Calculation
Fan Noise Calculation
Fan Application Pressure Calculation
Differences Between Forward-Inclined and Backward-Inclined Impellers

Total Pressure Total Pressure=Static Pressure+Dynamic Pressure 机外Static Pressure 机外Static Pressure△P=Rm*L(1+k) Pa 式中: Rm—单位长度风管摩擦阻力损失,Pa/m; L—最远送风口送风管总长加上最远回风口回风管总长,m; k—局部阻力损失与摩擦阻力损失的比值。 弯头三通少时,取k=1.0~2.0; 弯头三通多时,取k=3.0~5.0 此formula为简易估算formula,如果需要优化calculation,建议采用Static Pressure复得法 calculation,详见实用供热空调设计手册(第二版)11.6.3 P1157 机内Static Pressure 机内Static Pressure=各功能段(风机段除外)阻力之和 组合式空调器功能段空气阻力(Pa)(面风速为2.5m/s时) 以下数值仅供参考,具体数值建议咨询供应商 初效过滤器?????????????????????????????? 50 中效过滤器?????????????????????????????? 150 高效过滤器?????????????????????????????? 250 盘管(单排)?????????????????????????? 30 片式/微孔板消声段????????????????? 60/30